KB180 Gas Detection Controller

Compact gas detection controller for 4-20mA detector input, local alarm handling, relay output and RS485 / MODBUS upload workflows.

KB180 Gas Detection Controller business scene visual

Gas Detection & Alarm Control Systems

Product selection can be reviewed by installation environment, gas type and target-market requirements.

Answer Summary

Hanwei Smart Gas provides the KB180 Gas Detection Controller for compact industrial and commercial gas alarm systems. It accepts up to eight compatible 4-20mA fixed detectors and provides LCD status indication, local audible and visual alarms, two dry-contact relays and a DC24V pulse-valve output. RS485/Modbus supports monitoring-system integration. The controller belongs in a safe indoor area, while field detectors are selected for the actual gas and site conditions. Detector compatibility, valve type, wiring, output loads and certification coverage require confirmation for the project and target market.

Product Overview

KB180 coordinates up to eight compatible 4-20mA fixed gas detectors in a compact alarm control system. LCD and status indicators provide local visibility, while audible and visual alarms, two dry-contact relays and a pulse-valve output support response-device integration. RS485/Modbus provides a connection to an upper monitoring system. This is a safe-area controller rather than a field gas detector. Confirm detector power demand, cable design, output loads and the required response sequence before planning shut-off or ventilation linkage.

Product category

Gas Detection & Alarm Control Systems

Small commercial premises, commercial kitchens, utility rooms, small station areas and compact multi-point combustible gas monitoring projects.

Up to eight compatible 4-20mA fixed gas detector inputs

Controller-level alarm judgement with LCD / LED status indication

Local sound and light alarm handling for duty-room operation

Two dry-contact relays and a DC24V pulse-valve output for compatible devices

RS485 / MODBUS upload, subject to monitoring-system compatibility confirmation

Application Fit & Installation Boundary

Select products for the installation environment, gas type and system role.

Application fit

KB180 supports compact gas detection controller applications where 4-20mA fixed detectors and local response devices need coordinated alarm handling.

Installation context

Wall-mounted installation in a safe indoor area such as a monitoring room or duty room. Connected detectors are installed near the relevant gas-use or potential leak locations according to site assessment.

Selection boundary

KB180 is a controller, not a gas detector, gas meter, household alarm, field probe or inline pipeline device. Point count, 4-20mA transmission distance, linkage output and certification should be confirmed by model and market.

Typical Applications

Common gas safety scenarios where this product category can support monitoring, alarm verification or response workflows.

Small restaurants and small commercial premises gas monitoring

Commercial kitchen and gas equipment room alarm control

Shopping mall or underground corridor gas leak alarm projects

Compact 4-20mA detector plus controller packages

Local alarm, relay linkage and monitoring-record workflows

Product Selection Notes

Specifications to be confirmed by product model and target market.

Device roleGas detection controller.
Detector inputUp to 8 compatible three-wire 4-20mA fixed gas detectors. Confirm terminal wiring and detector power demand.
Data uploadRS485 supporting Modbus; confirm data mapping and monitoring-system compatibility.
Alarm / relay outputLocal audible and visual alarms; 2 dry-contact relays, maximum AC220V and <=3A. Verify load compatibility.
Pulse-valve outputFor compatible DC24V solenoid valves, DN50 or smaller; confirm valve type and wiring before use.
Power supplyMain: AC187-253V, 50Hz +/-5Hz. Backup: DC20-27V.
Consumption / output voltage<=10W, excluding gas detectors; output voltage DC20-28V.
DisplayLCD screen and status indicators.
Working temperature / humidity0-40°C; <=95% RH.
Dimensions / weight280 x 220 x 76 mm; <=5 kg.
InstallationIndoor safe-area wall-mounted controller installation; not for hazardous-zone field mounting.
CertificationCertification availability varies by product and target market. Contact us for confirmed specifications.

How It Fits Into a Project

A product category can be selected as part of a field-to-platform safety workflow instead of as an isolated device purchase.

14-20mA gas detector
2KB180 controller
3Sound / light alarm
4Relay / pulse output
5Fan / valve linkage
6RS485 / MODBUS upload
7Response record

Why Hanwei

Hanwei Smart Gas can support product selection within wider gas safety monitoring and local partner cooperation discussions.

Provides a compact controller path for small commercial and facility gas safety projects.
Connects compatible 4-20mA detector signals with local alarm handling and project-specific relay linkage.
Can be paired with Hanwei fixed gas detectors, warning devices and platform records by confirmed project scope.

Certification availability varies by product and target market. Contact us for confirmed specifications.

FAQ

Common questions for early product selection and project discussion.

Does KB180 detect gas directly?

No. KB180 is a gas detection controller. Gas detection depends on connected 4-20mA gas detectors, while KB180 handles controller-level alarm judgement, display, output and upload workflows.

Where should KB180 be installed?

KB180 is intended for wall-mounted installation in a safe indoor area such as a monitoring room or duty room. It is not an explosion-proof field device and is not intended for hazardous zones, outdoor rain exposure or installation directly beside a gas pipeline. Confirm the site and installation arrangement before use.

Can KB180 link with fans or shut-off valves?

Relay and optional pulse-valve outputs require compatibility checks for the selected fan, shut-off valve or other response device. Confirm the output configuration, device models, wiring and project design before use.

Can KB180 connect to an upper monitoring system?

RS485 / MODBUS upload is an integration option. Confirm model support, monitoring-system compatibility, data mapping and the integration scope before project use.

Are certifications available?

Certification availability varies by product and target market. Contact us for confirmed specifications.

Product Inquiry

Discuss product selection, pilot scope and target-market requirements with Hanwei Smart Gas.

Discuss Product Selection

Share the application scenario, target gas, installation environment and expected integration method so the appropriate product direction can be reviewed.